Posts Tagged ‘High Current Test’

Circuit Breaker Reset Tests

January 11th, 2012 Comments off
1600 Amp General Electric Air Circuit Breaker - Catalog No. AK-2A-50-1

1600 Amp General Electric Air Circuit Breaker – Catalog No. AK-2A-50-1 Available at www.swgr.com

A customer called MIDWEST to ask why we did something called a “Reset Test” on his circuit breaker. He said he has had circuit breakers tested by switchgear service companies for nearly 30 years and never ever saw something called a circuit breaker “Reset Test.” He has Square D circuit breakers, Westinghouse circuit breakers, General Electrical circuit breakers and newer Cutler Hammer circuit breakers. He checked some of his old test reports and found no “reset tests.”  He had never used MIDWEST before, so he was pretty interested when we explained the reason and procedure for the reset test. The reason was a very pleasant surprise because it gave him greater confidence in the proper performance of his circuit breakers.  MIDWEST started using the circuit breaker “reset test” many years ago. It’s not a standard test procedure. You won’t find it in the text books or instruction manuals. You will find it in MIDWEST’s Training Manual under ‘Scars,’ meaning experience. It’s a carry over procedure from testing old dashpot type air circuit breakers and insulated case circuit breakers and molded case circuit breakers. The reason for the test is that occasionally, seldom but occasionally, a circuit breaker will nuisance trip when put back into service after it has been high current tested. For example, a 1600 amp air circuit breaker, after high current testing, might nuisance trip instantly at 500 amps.  Basically the over current device failed during the high current testing. This was far more common with older “non electronic” over current devices. New electronic over current devices are more reliable, but not perfect. Strange things happen. We are not talking about the service technician forgetting to put the settings back to the correct positions. We are talking about an actual defective device. The test only takes moments. In the interest of quality control, the reset test addresses the “consequences of failure” as opposed to the “probability of failure.”

Yes, we are paranoid about safety and quality.

Circuit Breaker Trip Device – Hidden Defect

February 2nd, 2011 Comments off
 
Square D PAL362000 Circuit Breakers For Sale

Square D PAL362000 Circuit Breakers For Sale

MIDWEST asked our Switchgear Engineering Technicians for an example of a molded case circuit breaker that had a hidden defect that could only be found by experienced testing.  We find many used circuit breakers that have defects that can be found by a close visual inspection.  Sometimes the defect may not be obvious but an experienced Engineering Technician knows where to look and would find the problem. In the business of repairing and reconditioning circuit breakers, we find about every possible problem that can occur. Whether we are reconditioning a replacement Westinghouse, General Electric or Siemens circuit breaker, many of the problems are the same. But we also frequently find hidden defects that could only be detected using proper testing.

 

 

For this example, let’s just use a replacement Square D PAL362000 circuit breaker. The breaker was reconditioned, which involved removing the cover to thoroughly inspect and maintain the interior of the Square D circuit breaker. The technician was immediately suspicious because he detected the slight smell of an overheated circuit breaker. Once you get that smell in your nose, you never forget it in the future. Even a small whiff tells you there may be a problem. In this case everything visible was in very good condition. There were no signs of overheating at the contacts or the line or load side breaker terminals. But the contact resistance test results indicated very high resistance on the center pole. A DLRO, digital low resistance ohmmeter, was used to locate the problem. The usual location is either the contacts, the bolted connections to the trip device, or the line or load side terminals or lugs. In this case the defect was inside the trip device. And a close sniff of the trip element confirmed it. MIDWEST performed an additional test, a high current test, to determine the voltage drop and therefore the resistance in the trip device on the center pole. Even though this replacement Square D circuit breaker looked just great, the trip device was defect and had to be replaced.