Circuit Breaker Large Over Current Time Delays

December 29th, 2010 4 comments

In MIDWEST’s training classes for qualified personnel, there is a segment where we explain the long time delay range within which a Square D 1000 amp circuit breaker should trip due to an overload. This information is received with anything from amazement to skepticism to outright disbelief, even though we show the Square D circuit breaker characteristic trip curve.  The overload time delay information is not restricted to Square D circuit breakers. It’s the same with Cutler Hammer, GE General Electric, Siemens, ITE, Westinghouse, Merlin Gerin, or Federal Pacific circuit breakers.

 

In our training example we use an old Square D 1000 amp MA type circuit breaker.  If we tested this circuit breaker at 3000 amps, that’s 300%, the minimum to maximum trip range is about 45 seconds to 340 seconds. It might trip in 45 seconds or it might not trip for 340 seconds.  This is an old thermo-magnetic circuit breaker, which typically works by heating a bi-metal in the over current trip device. Many newer breakers use electronic over current devices which have more repeatable overload time delay test results.

 

The illusion is that these Square D, Cutler Hammer, Westinghouse circuit breakers are designed to directly protect people. They are not. The breakers protect the equipment connected to them and they protect the electrical system. They are designed for the characteristics of the equipment connected, such that connected equipment will not be damaged by an overload or fault. This is a basic limited explanation. So, when you think of molded case circuit breakers, power circuit breakers or air circuit breakers, it’s important to know these breakers don’t just trip right at the breaker trip device rating.