Archive

Posts Tagged ‘thermographic scan’

Circuit Breaker Infrared Scanning Disagreement – Lugs

October 27th, 2010 Comments off

Infrared Scan of a Circuit BreakerWe read about a disagreement between two bloggers over whether or not infrared scanning, or thermography, was needed if you torque tightened the wire connections to power circuit breaker terminals during routine maintenance.  What occurred to MIDWEST were all the possible deficiencies we find in old, new, and replacement circuit breakers, using infrared scanning, that have nothing to do with whether or not the load terminals were tight.  One of the nasty deficiencies is when the cable lug in an old circuit breaker is very tight, but the lug is overheating because the screw, holding the lug to the breaker output tab, is loose. We’ve seen brand new circuit breakers and replacement circuit breakers fry the load side tab of the breaker so bad that the breaker had to be replaced. This is true for new or old Square D, GE General Electric, Westinghouse, Siemens, Cutler Hammer, ABB, any manufacturer. It has nothing to do with a specific circuit breaker manufacturer.

 

Sometimes the lug is welded to the tab from the arcing between the lug and tab. There is a very sophisticated test one can perform during a maintenance outage to check for this defect. First, check for voltage at the load and line side of the de-energized circuit breakers. Don’t care that the main breaker is off and all the feeder breakers are open.  Check voltage anyway.  You are checking for something that shouldn’t be, not for something you know should be.  We, rather I, have personal experience with getting my hand blasted because a breaker was back fed. Very bizarre set up, unbelievable, just waiting to injure someone.

 

After checking for voltage, carefully and gently try to move the conductor coming out of each phase of each circuit breaker.  You are trying to see if the cable is loose in the lug and you are trying to see if the lug is loose, moves or turns, in the circuit breaker. You are not trying to force it to move. Just use enough force to see if it is loose in the circuit breaker. If the lug itself is loose, the cable or cables will need to be removed from the lug; The mounting screw for the lug properly tightened; The cables properly reinstalled; And the cables tightened in the lug. Again, don’t be too forceful. On small breakers, you can always make the lug move. Repeating, you just want to use enough force to see if the lugs for that old obsolete circuit breaker are loose.

 

If the conductive interface, between the lug and the circuit breaker, is damaged from severe overheating or arcing, the defective circuit breaker may need to be replaced. Sometimes the damaged area can be repaired.  MIDWEST does not recommend replacing power circuit breakers while the switchboard is energized. Be safe. Turn things off. Check for voltage everywhere.

Replacement Circuit Breaker Tight but Loose

June 4th, 2010 Comments off

During our annual Thermographic Scan of a large manufacturer’s electrical system, MIDWEST found a serious problem with a new circuit breaker. The middle line side bolted connection was extremely hot. They had recently installed a replacement circuit breaker with a higher interrupting current level in this panelboard.  During their Arc Flash Hazard Analysis they discovered several old circuit breakers that did not have high enough interrupting current rating for their system. So they replaced these circuit breakers.  The replacement circuit breakers had high interrupting ratings and it was a straight forward replacement project. Their electricians were pretty sharp, so they were skeptical of our finding.  On third shift they powered down and checked connections and the electricians informed MIDWEST, in their own emphatic vernacular, that the bolts were tight and maybe MIDWEST was loose.  MIDWEST has run into this breaker problem before.  It doesn’t happen often, but we work with old and new circuit breakers every day, all day.  Here is the work practice one must follow when changing out old circuit breakers.  Always lay out the bolts removed from the old circuit breaker such that you know exactly which bolt came out of which hole. Use identical replacements for each bolt and pay attention to the bolt lengths. Replace the bolts with new bolts of the exact same length.  On their installation, the middle line side bolt was shorter than the other two bolts. The middle bolt was not a through bolt. The bolt hole bottomed out.  They used a bolt that was ¼ inch too long and even when it was properly torque tightened, it still was not a physically tight connection, because the bolt hit bottom before the attached bus was tight. We suspect their torque wrench was called “armstrong,” so we were sure they had tightened it enough. Again, on third shift, they replaced the bolt with the right length and the overheating circuit breaker problem disappeared.  MIDWEST recommends following a simple work practice when installing replacement circuit breakers. Keep track of exactly which bolt went where. Usually it does not make a difference, but one in a hundred does.  This customer was lucky we did an infrared scan shortly after the circuit breaker was replaced.